Introduction
High performance, redundant power protection with scalable power
and runtime for space-constrained computer rooms and voice and data
networks
Engineered to deliver the highest level of business continuity
possible, the Symmetra LX uses a modular, redundant architecture
that can scale power and run-time as demand increases or when
higher levels of availability are required. Advancements in this
next generation design greatly decrease foot print or U-space
needed in an equipment rack, increase speed and ease of deployment
and reduce repair time. With built-in network manageability and a
comprehensive portfolio available from 4-16 kVA N+1, the on-line
Symmetra LX is the choice to protect high-performance IT and
telecom equipment in computer rooms and small data centers.
General Features
-
Audible Alarms
-
Automatic internal
bypass
-
Automatic restart of loads
after UPS shutdown
-
Automatic self-test
-
Battery modules connected in
parallel
-
Cold-start capable
-
Configurable for N+1 internal
redundancy
-
Disconnected battery
notification
-
Field-replaceable power
distribution panel
-
Frequency and voltage
regulation
-
Generator Compatible
-
Hot-swappable
batteries
-
Hot-swappable intelligence
modules
-
Hot-swappable power
modules
-
InfraStruXure Manager
Compatible
-
Input Power Factor
Correction
-
Intelligent Battery
Management
-
LCD display
-
Manageable external
batteries
-
Modular design
-
Network manageable
-
Plug-and-Play external
batteries
-
Power conditioning
-
Power Modules connected in
parallel
-
Predictive failure
notification
-
Programmable Frequency
-
Rack/Tower Convertible
-
Redundant Intelligence
Modules
-
Removable input/output wiring
tray
-
Resettable circuit
breakers
-
Safety-agency approved
-
Scalable Power
Capacity
-
Scalable runtime
-
SmartSlot
-
User-replaceable
batteries
-
User-replaceable intelligence
modules
-
User-replaceable power
modules
Technical Specifications
Output
-
Output power capacity: 8000
VA
-
Output power capacity: 5600
watts
-
Max Configurable Power: 16000
VA
-
Max Configurable Power: 11200
watts
-
Nominal output voltage:
230V
-
Output Voltage Note:
Configurable for 220 : 230 or 240 nominal output
voltage
-
Output Voltage Distortion:
less than 5% at full load
-
Output Frequency (sync to
mains): 47-63Hz
-
Crest Factor: up to 5 :
1
-
Waveform type:
Sinewave
-
Output Connections: (1) Hard
Wire 3-wire (H N + G)
Input
-
Bypass: Internal Bypass
(Automatic and Manual)
-
Nominal input voltage: 230V,
400V 3PH
-
Input frequency: 45 - 65 Hz
(auto sensing)
-
Input Connection Type:
-
Hard Wire 3 wire
(1PH+N+G)
-
Hard Wire 5-wire
(3PH + N + G)
-
Input voltage range for main
operations: 155 - 276, 290 - 480 (3:1) V
-
Other Input Voltages: 220V,
240V, 380V, 415V
Batteries &
Runtime
-
Battery type:
Maintenance-free sealed Lead-Acid battery with suspended
electrolyte : leakproof
-
Battery Slots Empty: 2
-
Replacement battery
cartridge: SYBT5
-
RBC Quantity: 2
-
Typical backup time at half
load: 20.2 minutes (2800 Watts)
-
Typical backup time at full
load: 7.5 minutes (5600 Watts)
-
Runtime Chart: Symmetra
LX
-
Extended run options: APC
Symmetra LX 8kVA Scalable to 16kVA N+1 Tower,
220/230/240V or 480/400/415V
Communications &
Management
-
Interface port: DB-9 RS-232 ,
Smart-Slot
-
Available Smart Slot
Interface Quantity: 1
-
Pre-Installed SmartSlot
Cards: AP9619
-
Control panel: Multi-function
LCD status and control console
-
Audible alarm: Audible and
visible alarms prioritized by severity
-
Emergency Power Off (EPO):
Yes
Physical
-
Maximum height: 37 inches (
93.73 cm )
-
Maximum width: 19 inches (
48.26 cm )
-
Maximum depth: 29 inches (
72.64 cm )
-
Net weight: 483 lbs. ( 219.55
kg )
Environmental
-
Operating Environment: 0 - 40
°C ( 32 - 104 °F )
-
Operating Relative Humidity:
0 - 95 %
-
Operating Elevation: 0-10000
feet ( 0-3000 meters )
-
Storage Temperature: -15 - 45
°C ( 5 - 113 °F )
-
Storage Relative Humidity: 0
- 95 %
-
Storage Elevation: 0-15000
feet ( 0-4500 meters )
-
Online thermal dissipation:
3707 BTU/hr